| Parameter | Specification |
|---|---|
| Impulse voltage grade | 100kV-7200kV |
| Standard lightning wave | 1.2±30%/50±20%µS |
| Peak oscillation | 5% |
| Standard switching wave | 250±20%/2500±60%µS |
| Virtual front time of oscillating lightning wave | 15µS |
| Virtual front time of oscillating switching wave | 15µS-1µS |
| Minimum output voltage | 10%Un |
| Charging voltage instability | 1% |
| Synchronizing range | 20% |
| Synchronous discharge error rate | 2% |
| Ignition range | 10%-100% |
| Working time | 70%UN Discontinuous work (charge-discharge 300s/time) 70%nn Continuous work (charge-discharge 120s/time) |
| Generator efficiency | Lightning wave (no load) - 90% |
| Time to chopping | 2-5µS |