Model: SXBTC 4-in-1 Transformer Power Analyzer
Alias: Transformer Capacity & Loss Tester, Iron & Copper Loss Tester
This integrated tester combines transformer capacity detection, loss testing, harmonic analysis and oscilloscope functions with high test accuracy. It can measure transformer capacity, no-load loss, short-circuit loss, impedance voltage, harmonic content and complete vector analysis.
With built-in three-phase high-power test source, it supports passive measurement without external power supply or regulators. Lightweight at only 3kg, equipped with English operation screen, storage and printing function, suitable for field inspection and factory testing of transformers 20kVA–100000kVA.
| Item | Parameter |
|---|---|
| Active Measurement | Voltage: 0~10V; Current: 0~10A |
| Passive Measurement | Voltage: 0~750V; Current: 0~100A auto-range |
| Precision | Voltage ±0.5%, Current ±0.5%, Power ±0.5% (CosΦ>0.2) / ±1.0% (0.02<CosΦ<0.2) |
| Test Capacity Range | 20kVA ~ 100000kVA |
| Working Temp | -10℃ ~ +40℃ |
| Charging Voltage | AC 160V~260V |
| Insulation | Terminal-shell insulation ≥100MΩ, 2kV 1min withstand voltage |
| Dimension | 32cm × 24cm × 13cm |
| Weight | 3kg |
| Storage | 200 groups test data |
Advantages: Factory direct supply, high precision complying with industry standards, portable offline testing, full English supporting documents.
![]()
![]()
![]()
![]()
![]()