Product Description
The SXBP Variable Frequency Series Resonance Test System is a professional high-voltage testing solution designed for AC withstand voltage testing of large-capacity, high-voltage electrical equipment. This system delivers stable, accurate, and repeatable test results for a wide range of capacitive test objects in power systems, substations, and power transmission projects.
Technical Specifications
| Item | Specification |
|---|---|
| Rated Capacity | 300 kVA – 20,000 kVA |
| Rated Test Voltage | 200 kV – 2,000 kV |
| Rated High-Voltage Current | 1 A – 100 A |
| Power Supply | 380 V, 50 Hz / 60 Hz |
| System Quality Factor | Q ≥ 50 |
| Output Frequency Range | 20 Hz – 300 Hz |
| Frequency Adjustment Resolution | 0.1 Hz |
| Frequency Instability | ≤ 0.05% |
| Output Waveform | Sine wave |
| Waveform Distortion Rate | ≤ 1% |
| Continuous Running Time | 60 minutes at rated condition |
| Noise Level | ≤ 65 dB |
| Temperature Rise | Coil temperature rise ≤ 65 K after 60 minutes of rated operation |
Key Applications
-AC withstand voltage testing of 110kV, 220kV, and 500kV long-distance XLPE power cables
-On-site commissioning and preventive testing of GIS (Gas Insulated Switchgear)
-Withstand voltage testing of power transformers, instrument transformers, bushings, and insulators
-Testing of capacitive voltage transformers (CVT), coupling capacitors, and other capacitive apparatus
-High-voltage acceptance tests for substations, transmission lines, and power distribution projects
FAQ
Q1: What types of high-voltage equipment can the SXBP system test?
A: It can be used for AC withstand voltage testing of XLPE cables, GIS, power transformers, instrument transformers, CVTs, bushings, insulators, coupling capacitors, and other capacitive high-voltage apparatus.
Q2: Can this system be used for on-site testing?
A: Yes. The SXBP system is designed for field applications. Its modular configuration and relatively low input power requirements make it suitable for use in substations, construction sites, and outdoor testing environments.
Q3: What power supply is required for operation?
A: The system is typically operated from a 380 V, 50 Hz/60 Hz industrial power supply. Because series resonance multiplies the effective test voltage, the required input capacity is much lower than the apparent test capacity.
Q4: Is the frequency adjustable for different test objects?
A: Yes. The output frequency is adjustable from 20 Hz to 300 Hz, which allows the system to adapt to different capacitive loads and meet the test frequency requirements of various high-voltage apparatus.